Designers of the HOTJET manage to fit our heat pumps in any small spaces of 0.5 m3. HOTJET-i can be installed in house interiors, e.g. in cellars, garages or in spaces for a building equipment. Atmospheric air is supplied and drained by air lines through a wall.

HOTJET i nerez

 Benefits:


  • Compact unit
  • Indoor installation 
  • Guard cover is made of stainless steel sheet or powder coating
  • The maximum flow temperature to 55 ° C
  • Sound-optimised through low-noise axial-flow fan 
  • Central control of heating and heating of DHW
  • Suitable for floor and radiator systems
  • Wired and wireless control
LOGO TUV SUD vyrobeno-v-ceske-republice
Integrated as standard :
  • The electric elements
  • The controller Siemens basic RVS41

Modell 
8i 11i 15i

Performance data

EN14511

Power output / input / COP   
A7/W35 7,8 / 2,04 / 3,8 9,3 / 2,45 / 3,8 10,8 / 2,79 / 3,8
A2/W35
7,2 / 2,01 / 3,6 8,6 / 2,39 / 3,6 10,1 / 2,76 / 3,6
A7/W45 7,4 / 2,46 / 3,0 8,8 / 2,93 / 3,0 10,3 / 3,39 / 3,0
A2/W45 6,6 / 2,46 / 2,7 8,0 / 2,96 / 3,0 9,3 / 3,44 / 2,7

Technical data

Model 8i 11i 15i

Temperature limit of suction air

-20 °C to 35 °C

Temperature limit of heating system 

+15 to +55°C (below outdoor temperature -10°C max. output temperature 50°C) 

Heating and reversing water communication pipe

1"

Volume rate of flow, heating side 

1,3 m3/h

1,5 m3/h

1,8 m3/h

Head loss, heating side

<20 kPa

Protection of heating water against freeze-up

Yes

Rate of air flow in the primary side 

2 200 m3/h

2 200 m3/h

2 200 m3/h

Air channel diameter

400 mm

Refrigerant circuit

Refrigerant 

R407C

R404A

R407C

Refrigerant quantity

2,1

2,3

2,4

Defrosting 

Automatic, according to the need. Upon request (manual)

Way of defrosting

By hot Refrigerant (reversal) 

Heating of the condensate bulk tank 

yes

Condensate drainage 

By a hose

Cut-off pressure of low-pressure 

0,08 MPa

Cut-off pressure of high-pressure 

2,8 MPa

Technical information, weight

width x depth x height [mm]

1040 x 632 x 902

Weight 

210 kg

210 kg

215 kg

placement

Designed for internal installation (there are holes on the walls for air suction and air outlet)

Anti-corrosive protection  

powder coat, galvanized sheet, cataphoresis 

Colour

RAL 7036

Degree of protection ( EN 60 529 ) 

model i: IP40

Electrical data

Power supply

400 V / 3 / 50 Hz

Compressor 

Copeland scroll

Service current [A]

4.5

5

5.8

Starting current [A

18

20

23

Maximum service current [A]

6.5

7

8.8

Compressor protection [A]

16B

16B

20B

Compressor supply line

5 x 2,5 (n x mm2)

Noise level  

Sound power Lw [dB(A)]

HOTJET i: 57 dB

Sound pressure Lp [dB(A)]

   HOTJET i: 44,9 dB

Equipment 

Control electronics Siemens RVS41

yes (optional RVS61)

Operator panel AVS37 on the device

yes

Wireless device QAA78

optional

External switchboard with electronics 

optional (the whole wiring system is housed in external switchboard)

Soft start unit

optional Danfoss

Condensate pump

optional

Integration into cascade

Up to 16 heat pumps or mixed sources are supported 

Bivalence (back-up power supply)

External tubular electric boiler 

optional  (3x phases 2,5 / 5 / 7,5 kW)

Electric cartridges in storage reservoir

supported

External gas or electric boiler 

supported

Electric post heating of boiler

supported

Solid  fuel boiler

supported discharge of storage reservoir if it is overheated  

 *) Values as A2/W35 mean: intake air temperature is 2 ° C, outlet water temperature from the heat pump is 35 ° C. Values are reported according to standards EN 14511-1 to 4:2005

Installation pictures 

  Hotjet priklad kotelnyTepelné čerpadlo HOTJET i - instalace příklad 4